Details
Factory | Hospital | Office | Access Flooring | Electronic | IT |
LG Hausys Floors
TECHNICAL DATA | ||||
Static Pulse | ||||
|
||||
Item | Standard Test Method | Specification | Conductive Tile | Dissipative Tile |
|
||||
Electrical/ Electrostatic Properties | ||||
Electrical Resistance | ESD S 7.1 | Static Conductive : 2.5 x 104 ~ 106Ω |
2.5 x 104 ~ 106Ω | 106 ~ 109Ω |
ASTM F 150 | Static Dissipative : 106 ~ 109Ω |
|||
Static Generation | AATCC-134 | 0.1KV | 0.2KV | |
Static Decay | Federal Test Method 101B Method 4046 |
< 0.5 sec | 0.01 sec | 0.01 sec |
|
||||
Other Properties | ||||
Classifcation | EN 685 | Class 34 + 43 | ||
Composition Of Material | ASTM F 1700, Certifcate of Compliance |
Homogeneous | ||
Thickness | ASTM F 386, EN 428 | as specifed ± 0.13mm | Meets Standard | |
Nominal Sizes | ASTM F 536, EN 427 | <± 0.4mm / 304.8mm | Meets Standard | |
Squareness | ASTM F 2055 | maximum 0.25mm | Meets Standard | |
Residual Indentation | ASTM F1914, EN 433 | average less than 8%, max. single reading 10% |
< 8 % | |
Flexibility | ASTM F 137 | no crack or break | No crack or break | |
Dimensional Stability | ASTM F 2199, EN 434 | < 0.51mm / 304.8mm | Meets Standard | |
Resistance To Chemicals | ASTM F 925, EN 423 | no more than a slight change in surface dulling, surface attack, or staining |
No more than a slight change in surface dulling, surface attack, or staining |
|
Resistance To Heat | ASTM F 1514 | ΔE < 8 ave., max | Meets Standard | |
Resistance To Light | ASTM F 1515 | ΔE < 8 ave., max | Meets Standard | |
Static Load Limit | ASTM F 970-93 | - | 0.005”(at 2500 psi), 0.127mm(at 175kgf/cm2) | |
Smoke Density | ASTM E 662 | < 450 | < 450 | |
Flame Spread | ASTM E 84, NFPA 225 | < 75 | ||
Thermal Conductivity | DIN 52612 | 0.309 W/(m.k) | ||
Critical Radiant Flux | ASTM E 648, NFPA 253 | Class 1 ( > 0.45 w/cm2) | ||
Abrasion Resistance | ASTM D 1044, CS-10-F Wheel, 500gm Weights | Cycl | % Gauge Loss | |
2,500 | 0.22 | |||
5,000 | 0.44 | |||
7,500 | 0.65 | |||
10,000 | 0.86 | |||
Resistance To Wear | EN 660-1 | Group M | ||
Castor Chair Suitablilty | EN 425 | No damage | ||
Color Fastness | EN ISO 105 B02 | At least 6 | ||
Standard For Health Care Facilities | NFPA 99 | Confrms to the requirement of NFPA 99 in effect at the time of installation | ||
Fulflls Product Requirements | EN 649 | Yes | ||
Underwriters Laboratories | UL 779 | Meets UL Standard | ||
Burning Characteristics | EN 13501-1 | Bfl-S1 | ||
|
||||
Warranty | ||||
Guarantee For Manufacturing Defects And Wear-Out* |
No Damage | 5 Years | ||
Conductivity* | Lifetime |
View more about C6111 on main site